The OMNIX350HG offers medical-grade UPS protection with built-in line-interactive voltage regulation. IEC320 plug and outlets, plus built-in isolation transformer with Faraday shield offer full isolation and remove common mode noise. Tested to CE/IEC 60601-1 as medical electrical equipment. 350VA power handling capacity supports computers, inter-networking equipment and other critical loads during commercial power failures. Line-interactive voltage regulation corrects brownouts as low as 159V back to normal 230V levels, saving battery reserves for use only during complete power failures. Includes two-line phone surge suppression and built-in USB communications port.
This UPS contains a lead acid battery designed to be connected continuously to an AC power source, except during brief power outages. It is not intended for frequent charge/discharge cycles, such as mobile cart applications where the UPS is often disconnected from the power source. Using the OMNIX350HG in this type of application will void the battery warranty.
- Ideal UPS protection for applications in medical patient-care areas where CE/ IEC 60601-1 electrical medical equipment is required
- Line-interactive voltage regulation corrects brownouts as low as 159V without using battery power
- IEC320 plug and outlets offer added degree of safety and reliability to input/output connections
- Full line isolation prevents shock potential and operational problems in sensitive electronic equipment
- Resistant to electrostatic discharge
- Supports loads up to 350VA/225 watts
- 37 minutes half load runtime (with 175VA load), 15.5 minutes full load runtime (with 350VA load)
- 6 protected outlets; 6-inch dongle with IEC C14 inlet
- C14 inlet accepts user-supplied AC power cord with grounded country-specific plug
- 1-USB port for monitoring interface
- Complete surge protection, line isolation and EMI/RFI noise filtering
- 2 phone line surge suppression for modems, fax machines and other phone accessories
- 4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace
- Battery replacement door and back panel equipotential connection (grounding lug)
- Ground Potential Equalization Connector: POAG-S6/20
- OMNIX350HG Hospital Grade UPS System
- USB communication and telephone cables included
- Warranty information
- Instruction manual
OVERVIEW
| UPC Code | 037332140432 |
| UPS Type | Line-Interactive |
INPUT
| Input Phase | Single-Phase |
| Rated input current (Maximum Load) | 1.8A |
| Nominal Input Voltage(s) Supported | 230V AC |
| UPS Input Connection Type | C14 inlet |
| UPS Input Connection Description | C14 inlet accepts user-supplied AC power cord with grounded country-specific plug |
| UPS Input Cord Length (ft.) | 0.50 |
| UPS Input Cord Length (m) | 0.2 |
| Recommended Electrical Service | 10A 230V |
| Voltage Compatibility (VAC) | 230 |
OUTPUT
| Output Capacity (VA) | 350 |
| Output Capacity (kVA) | 0.35 |
| Output Capacity (Watts) | 225 |
| Output Capacity (kW) | 0.225 |
| Nominal Voltage Details | 230v nominal inverter output voltage |
| Frequency Compatibility | 50 / 60 Hz |
| Frequency Compatibility Details | Automatic frequency selection |
| Output Voltage Regulation (Line Mode) | -18%, +8% |
| Output AC Waveform (Battery Mode) | PWM sine wave |
| Nominal Output Voltage(s) Supported | 220V; 230V; 240V |
| Output Receptacles | (6) C13 |
BATTERY
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Runtime Full Load (min.) | 15.5 min. (225W) |
| Runtime Half Load (min.) | 37 min. (113W) |
| DC System Voltage (VDC) | 12 |
| Battery Recharge Rate (Included Batteries) | Less than 7.2 hours from 10% to 90% |
| Battery Access | Battery access door allows hot-swap battery replacement without powering connected equipment off |
| Internal UPS Replacement Battery Cartridge | RBC52 (quantity 2) |
| Typical Battery Lifespan | 3-6 years, depending on usage |
VOLTAGE REGULATION
| Voltage Regulation Description | Line interactive UPS offers a single boost level of brownout correction to maintain usable, computer grade output |
| Undervoltage Correction | Input voltages between 159 and 199 are boosted by 14% |
USER INTERFACE, ALERTS & CONTROLS
| Switches | Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions |
| Audible Alarm | Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will resume when approximately 2 minutes of battery operation remain (assuming full load) |
| LED Indicators | 4 LEDs indicate line power, battery power, overload and battery low/replace status |
SURGE / NOISE SUPPRESSION
| EMI / RFI AC Noise Suppression | Yes |
| AC Suppression Response Time | Instantaneous |
| Dataline Suppression | 2-Line Tel/DSL |
PHYSICAL
| Primary Form Factor | Tower |
| Cooling Method | Convection |
| Installation Form Factors Supported with Included Accessories | Tower |
| Installation Form Factors Supported with Optional Accessories | Wallmount ( UPSWM - tower mounting kit) |
| Primary UPS Depth (mm) | 188 |
| Primary UPS Height (mm) | 269 |
| Primary UPS Width (mm) | 132 |
| Shipping Dimensions (hwd / cm) | 35.89 x 26.49 x 20.90 |
| Shipping Weight (kg) | 12.43 |
| UPS Housing Material | PVC |
| UPS Power Module Dimensions (hwd, cm) | 26.92 x 13.21 x 18.80 |
| UPS Power Module Weight (kg) | 11.52 |
| Unit Weight (kg) | 11.52 |
ENVIRONMENTAL
| Operating Temperature Range | 32° to 104°F (0° to 40°C) |
| Storage Temperature Range | 5° to 122°F (-15° to 50°C) |
| Relative Humidity | 0 to 95%, non-condensing |
| AC Mode BTU / Hr. (Full Load) | 15.6 |
| Battery Mode Heat Dissipation (BTU/Hr) @ Full Load | 124.5 |
COMMUNICATIONS
| Network Management Card Description | Network management not supported |
| Communications Interface | USB |
LINE / BATTERY TRANSFER
| Transfer Time | 5 milliseconds AC to battery; 8 milliseconds battery to AC |
| Low Voltage Transfer to Battery Power (Setpoint) | 159 |
| High Voltage Transfer to Battery Power (Setpoint) | 266 |
FEATURES & SPECIFICATIONS
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported |
| High Availability UPS Features | Surge/noise protection |
| Grounding Details | Ground Potential Equalization Connector: POAG-S6/20 |
APPLICATIONS
| UPS Applications | Hospital/Medical |
STANDARDS & COMPLIANCE
| Product Certifications | IEC 60601-1 |
| Product Compliance | RoHS; CE (Europe); FCC Part 15 Class B (USA) |
WARRANTY & SUPPORT