The PDUMNH32HVAT 7.7kW Single-Phase 200-240V Monitored Automatic Transfer Switch/ATS PDU provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 1U of space in EIA-standard 19-inch racks and has one IEC 309 32A Blue outlet for connecting a single device or an additional 230V multi-outlet PDU with IEC 309 32A Blue plug, such as the PDUMV32HV.
Dual 10-foot (3.1-meter) input cords, each with IEC 309 32A Blue input plug, connect to any two separate primary and secondary input power sources, including out-of-phase input sources. The PDU constantly evaluates the power quality of both inputs. To ensure connected equipment remains powered, dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 15 milliseconds if the primary source fails or becomes unstable.
Built-in LX Platform network management interface allows remote access to the PDU for power monitoring, configuration, control and to receive user-configurable notifications. The Java-free LX Platform HTML5-based network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. Provides real-time load/current data with billing-grade accuracy (±1 percent). It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separate) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
Primary and Secondary Inputs for Power Redundancy
- Enables redundant power configurations for network devices with a single input cord or other non-redundant power supply configuration
- Two IEC 309 32A Blue (2P+E) inputs, each with 10-ft. (3.05 m) cord, connect to separate primary and secondary input power sources
- Any two input power sources are supported for primary and secondary inputs, including out-of-phase power sources
Built-In IEC 309 32A Blue Outlet
- Power a single 32A plug-in device or multiple network devices through a connected 32A 200-240V multi-outlet PDU, such as PDUMV32HV metered PDU input (sold separately)
Automatic Transfer Switching
- Dynamic solid-state (TRIAC) automatic transfer switching
- Switches to secondary power source if primary source fails or becomes unstable
- 1-5 ms transfer time ensures uninterrupted operation of connected equipment
- Built-in processor monitors power sources and prevents switching if secondary source is unavailable or of lower quality than primary source
Touchscreen LCD
- Reports input status for primary and secondary power sources, power availability, line voltage, frequency, amps, kilowatts and power factor
Advanced Network Monitoring
- Pre-installed WEBCARDLX with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities
- PADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations
Broad Communications Compatibility
- Java-free LX Platform HTML5-based network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH
- Supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network
- Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
- 10/100 Mbps auto-sensing for communication with 10/100 Base-T networks
Mounts Horizontally in 1U of Rack Space
- Compatible with EIA-standard 19 in. 4-post racks and rack enclosures
- Included PDU4PKIT rail kit adds rear rack-mounting support
- PDUMNH32HVAT 7.7kW Single-Phase 200-240V ATS/Monitored PDU
- Rack-mounting brackets
- PDU4PKIT rear support rail kit
- Owners manual
OVERVIEW
| UPC Code | 037332187871 |
| PDU Type | Monitored; Auto-Transfer Switch |
INPUT
| Input Phase | Single-Phase |
| PDU Input Voltage | 200; 208; 220; 230; 240 |
| Recommended Electrical Service | Two single-phase 32A 200-240V circuits |
| Maximum Input Amps | 32 |
| PDU Plug Type | (2) IEC-309 32A BLUE (2P+E) |
| Input Cord Details | Set of two inputs connect to separate PRIMARY and SECONDARY power sources |
| Input Cord Length (m) | 3.05 |
OUTPUT
| Output Capacity Details | 7.7kW (240V), 7.4kW (230V), 7.0kW (220V), 6.7kW (208V), 6.4kW (200V) total capacity; 32A maximum |
| Frequency Compatibility | 50 / 60 Hz |
| Output Receptacle Details | Output receptacle is on a 61cm / 24 inch cordset |
| Output Receptacles | IEC309 32A BLUE (2P+E) |
| Output Nominal Voltage | 200-240V |
USER INTERFACE, ALERTS & CONTROLS
| Front Panel LCD Display | Digital display reports input current in amps (Source A, Source B), output kilowatts (total), input voltage (Source A, Source B), input frequency (Source A, Source B) and output power factor |
| Front Panel LEDs | Front panel LEDs confirm amp (A) / kilowatt (kW) / voltage (V) / frequency (Hz) and power factor (PF) reporting information; Additional set of LEDs indicate Source A and Source B inputs for preferred, available and in-use status |
| Switches | ENTER and MODE switches toggle the digital display to display all reported information |
| Current Measurement Accuracy (Amps) | +/-1% |
| Voltage Measurement Accuracy (Volts) | +/-1% |
| Power Measurement Accuracy (Watts) | +/-1% |
PHYSICAL
| Material of Construction | Metal |
| Form Factors Supported | 1U rackmount |
| Included Mounting Accessory Description | Included mounting rails compatible with rack depth settings from 57.9 to 91.5cm (22.8 to 36 inches) |
| Minimum Required Rack Depth (cm) | 44.45 |
| PDU Form Factor | Horizontal (1U) |
| Shipping Dimensions (hwd / cm) | 18.29 x 54.10 x 57.15 |
| Shipping Weight (kg) | 9.80 |
| Unit Dimensions (hwd / cm) | 4.4 x 43 x 35.6 |
| Unit Weight (kg) | 8.28 |
ENVIRONMENTAL
| Operating Temperature Range | 32° to 122°F (0° to 50°C) |
| Storage Temperature Range | -22° to 140°F (-30° to 60°C) |
| Relative Humidity | 5% to 95% non-condensing |
| Operating Elevation (ft.) | 0-10,000 |
| Operating Elevation (m) | 0-3000 |
COMMUNICATIONS
| PowerAlert Software | LX Platform Interface: PowerAlert Device Manager |
| Communications Cable | Micro-USB- to-USB A configuration/console Access cable |
| Network Monitoring Port | RJ45 Network port, Micro-USB Configuration port, USB A port supports a variety of Envirosense2 environmental and control modules. See Accessories>Management Hardware section for more information about these modules. |
| SNMP Compatibility | Pre-installed LX platform interface provides remote monitoring via Java-free HTML5 web interface, telnet, SSH and SNMP management systems |
| Network Compatibility | 10 Mbps; 100 Mbps (Fast Ethernet) |
FEATURES & SPECIFICATIONS
| High Availability PDU Features | Auto-Transfer Switching |
STANDARDS & COMPLIANCE
| Product Certifications | EN 60950-1 |
| Product Compliance | RoHS; CE (Europe); FCC Part 15 Class A (USA) |
WARRANTY & SUPPORT
| Product Warranty Period (Worldwide) | 2-year limited warranty |